PowerVar Security Plus UPS in George Hall

Tags ups george

The PowerVar Security Plus UPS (model ABCDEF6000-22) was installed on 2021-08-24.
It powers all three data closets in George Hall.
This is an image of the front panel:

Uploaded Image (Thumbnail)

  • As long as the Line & INV buttons are green, the unit is healthy.
  • If the BYPASS button is amber, contact Exponential Power for support.
  • If the FAULT button is red, contact Exponential Power for support.
  • If you lose power to the data closets and the Line button is green, press the NORMAL/BYPASS button.
  • If you still do not have power to the data closets after pressing the NORMAL/BYPASS button, you will need to
  • mechanically bypass the UPS by disconnecting the power cable leading out of the box labeled “Feed For UP1”
  • from the UPS, and connecting it directly to the to the box labeled “EM”. You will need to disconnect the cable
  • from the box labeled “EM” to do this (see image below for reference):Uploaded Image (Thumbnail)
  • “Feed For UP1” provides power coming into the building.
  • “EM” provided power to the data closets.

See KeePass for contact information.